Warranty: | 1 Year |
---|---|
Product Name: | Tan Delta Tester |
Voltage Range: | 0.5-10kv |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Accuracy | Cx | ±(reading×1%+1pF) | |
tgδ | ±(reading×1%+0.00040) | ||
Anti-interference index | variable-frequency anti-interference, under 200% interference can still achieve the above accuracy | ||
Capacitance Range | internal HV | 3pF~60000pF/10kV 60pF~1.2μF/0.5kV | |
external HV | 3pF~1.5μF/10kV 60pF~30μF/0.5kV | ||
resolution | Max: 0.001pF,4 digits | ||
tgδrange | Unlimited, resolution of 0.001%, automatically identify the tested samples of capacitance, inductance and resistance. | ||
Test CurrentRange | 10μA~5A | ||
Power | 2kVA | ||
Internal HV | Voltage range | 0.5~10kV | |
Max output current | 200mA | ||
Step-up and step-down voltage mode | Continuous smooth adjustment | ||
Test Frequency | 45,50,55,60,65Hzsingle-frequency 49/51Hz,45/55Hz,47.5/52.5Hz automatic dual variable-frequency |
||
Frequency Accuracy | ±0.01Hz | ||
External HV | When forward wiring the max test current is 5A, power frequency or variable frequency is 45-65Hz | ||
When reverse wiring the max test current is 10kV/5A, power frequency or variable frequency is 45-65Hz | |||
CVT self-excited method low voltage output | Output voltage 3 ~ 50V, output current 3 ~ 30A | ||
Measuring time | About 30 s, correlate with the measurement mode | ||
Input Power | 180V~270VAC,50Hz/60Hz±1% ,Mains or generator power supply | ||
Computer Interface | Standard RS232 interface (Optional) | ||
Printer | Comes with mini thermal printer | ||
Temperature | -10ºC~50ºC | ||
Relative Humidity | <90% |