After-sales Service: | 1 Year |
---|---|
Warranty: | 1 Year |
Product Name: | Insulation Oil Dielectric Loss Tester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Working condition | -15ºC~40ºC RH<80% | |
Power | AC220V±10% Frequency Unlimited | |
AC high voltage output | 400V~2200V ±2% interval 100V 50VA | |
DC high voltage output | 200V~600V ±2% interval 50V | |
Temperature control induction furnace | 50VA;output current:25mA | |
Temperature control induction furnace | Maximum power 500W | |
Temperature control range | <100ºC | |
Temperature control error | ±0.5ºC | |
Temperature measurement resolution | 1ºC | |
Temperature control time | Room temperature to 90 ºC, less than 20min | |
Measuring range | tgδ | Unlimited |
Cx | 15PF~300PF | |
Rx | 10M-20T | |
Resolution | △tgδ | 0.001% |
△Cx | 0.01pF | |
△Rx | 0.01 | |
Accuracy | △tgδ | ±(reading×0.5%+0.020%) |
△Cx | ±(reading×0.5%+0.5PF) | |
△Rx | ±reading×10% | |
Relative dielectric constant | εr | automatic calculation according to Cx |
Volume resistivity | ρ | automatic calculation according to Rx |
Dimension | 450×310×360mm3 | |
Weight | 18kg | |
Distance between HV and LV | 2mm | |
Capacitance of hollow cup | 60±2PF | |
The maximum measurement voltage | Power frequency 2000V | |
Dielectric loss of hollow cup | tgδ<1×10-4 | |
Liquid capacity | About 40ml | |
Electrode material | stainless steel | |
Dimension | 70mm(D)×120mm(H) |