Uhv-370 Transformer Winding Deformation Short Resistance Tester

Product Details
After-sales Service: 1 Year
Warranty: 1 Year
Index Name: Transformer Short Circuit Impedance Tester
Diamond Member Since 2022

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Cooperated with Fortune 500
This supplier has Cooperated with Fortune 500 companies
Experienced Team
The supplier has 6 foreign trading staff(s) and 3 staff(s) with over 6 years of overseas trading experience
Patents Awarded
The supplier had awarded 1 patents, you can check the Audit Report for more information
Management Certification
The supplier has quality management system certification, including:
ISO9001:2015 certificate
ISO14001
ISO45001:2018 certificate
to see all verified strength labels (28)
  • Uhv-370 Transformer Winding Deformation Short Resistance Tester
  • Uhv-370 Transformer Winding Deformation Short Resistance Tester
  • Uhv-370 Transformer Winding Deformation Short Resistance Tester
  • Uhv-370 Transformer Winding Deformation Short Resistance Tester
  • Uhv-370 Transformer Winding Deformation Short Resistance Tester
Find Similar Products

Basic Info.

Model NO.
UHV-370
Scope of Voltage Measurement
5~400V
Scope of Current Measurement
0.1~20A
Power Frequency
50Hz
Ambient Humidity
≤85%Rh
Accuracy of Measurement
0.2D
Operating Power
AC220V±10%
Operating Temperature
-10ºC~50ºC
Net Weight
6kg
Transport Package
Wooden Case or Carton
Specification
CE/ISO
Trademark
UHV
Origin
China
Production Capacity
200 Sets Per Month

Product Description

Product overview
Transformer LV Short-circuit Impedance Tester applies to LV load impedance test during delivery, overhaul, trial test and handover test of power transformers (single phase or three-phase).
It tests the short-circuit impedance (%) of power voltage on site and compares it with the value indicated on the nameplate or the factory default to find out any defects including but not limited to winding displacement or deformation due to currents from major failure during transformation, installation or operation following the delivery test. (The short circuit change shall be considered as significant if it exceeds ± 3% as specified in China International Conference on Electricity Distribution 2000 ("CICED 2000")).
Transformer LV Short-circuit Impedance Tester is not provided with an external voltage regulator and adopts the primary connection mode. It begins the three-phase testing and calculates impedance error percentage automatically when the parameter is entered and provides intuitive results. This is a rapid tester which detects winding deformation of transformers on site
Uhv-370 Transformer Winding Deformation Short Resistance Tester
Uhv-370 Transformer Winding Deformation Short Resistance Tester

Products features
1,The tester is supplied with AC220V low voltage power to provide current for AB, BC and CA high voltage windings of the transformer automatically; collects data simultaneously and; calculates impedance error percentage automatically with intuitive testing results;
2,The tester completes the three-phase testing automatically in the primary connection mode other then inversed connection with the testing wire;

3,The tester allows either single phase testing or three-phase testing both manually and automatically;
4,The tester achieves output current limit applicable to test item with any impedance;
5,The test item can be measured without an external voltage regulator;
6,The tester functions in measuring zero sequence impedance;
7,The tester functions in measuring inductance;
8,The tester has a large LCD display with a menu in Chinese. Operation are facilitated based on the notes on the display; and
9,The tester enables printing and storage and is featured with high testing accuracy, high automation, small in size and light weight.


Product Parameter
Technical Parameters
Scope of voltage measurement: 5~400V Accuracy of measurement: 0.2d
Scope of current measurement: 0.1~20A Operating power: AC220V±10%
Power frequency: 50Hz Operating temperature: -10ºC~50ºC
Ambient humidity: ≤85%RH Net weight: 6kg


 

 