DC resistance of transformer is a must-test item of semi-finished product, finished product factory test, installation, handover test and preventive test of power department in transformer manufacturing, which can effectively find manufacturing defects such as material selection, welding, loose connection parts, missing strands, broken wires and other hidden dangers after operation.
The transformer DC resistance tester is an innovative product with a built-in large-capacity lithium battery, which is small in size and easy to carry. The product is not only suitable for the measurement of inductive test products such as transformers, transformers, reactors, but also suitable for the measurement of resistive test products such as copper bars, wires, switch contacts, etc. The instrument test speed is fast and the accuracy is high.
1,Lithium battery power supply or 220V AC power supply adaptive, one charge, can continuously carry out hundreds of transformer DC resistance test, the test process is simple and convenient.
2,Output six current, maximum output 10A current, maximum output 25V voltage, and can automatically select the current, convenient and fast.
3,Wide range, high precision, 500uΩ ~ 50kΩ.
4,With resistance temperature conversion function.
5,It has a variety of protection functions such as anti-electromotive force protection, break line protection, power failure protection, overheating alarm and so on.
6,5.6 inch large industrial high brightness color LCD screen, the display is still clearly visible in strong sunlight.
7,Equipped with external printer for easy data printing.
8,Has local storage and flash drive storage.
Direct resistance test | |||
Current gear | Measuring range | Current gear | Measuring range |
10A | 500uΩ~200mΩ | 100mA | 10Ω~200Ω |
5A | 10mΩ~1Ω | 10mA | 50Ω~2kΩ |
1A | 100mΩ~20Ω | 1mA | 500Ω~50kΩ |
Technical index | |||
accuracy | ±(Reading x 0.2%+2 words) | Maximum resolution | 0.1uΩ |
Conditions of use and appearance | |||
Working power supply | Built-in lithium battery or external charger, charger input 100 ~ 240VAC, 50Hz/60Hz | ||
Charging voltage | 16.8V | Charging current | ≤2A |
Charging time | About 4 hours | Service time | More than 8 hours |
Main engine weight | 3.6kg(excluding test line) | Main engine size | 325×225×125mm3 |
Service temperature | -10ºC~50ºC | Relative humidity | ≤90%, no condensation |