Warranty: | 1 Year |
---|---|
Product Name: | CT PT Analyzer |
Equipment Output: | 0-2500V, 5kVA |
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
Item | Parameter | |
Power supply | AC220V±10% ,50Hz | |
Equipment output | 0~2500Vrms, 5kVA(Maximum setting value 20A) | |
High current output | 0~1000A | |
Excitation measurement accuracy | ≤0.5%(0.2%*reading+0.3%*range) | |
Secondary winding resistance measurement | range | 0.1~300Ω |
accuracy | ≤0.5%(0.2%*reading+0.3%*range) | |
Second actual load measurement | range | 5~500VA |
accuracy | ≤0.5%(0.2%*reading+0.3%*range)±0.1VA | |
Phase measurement (angle difference) | accuracy | 4min |
resolution | 0.1min | |
CT turns ratio measurement | range | ≤25000A/5A(5000A/1A) |
accuracy | ≤0.5% | |
PT turns ratio measurement | range | ≤500kV |
accuracy | ≤0.5% | |
Working environment | temperature | -10ºC ~ 40ºC |
humidity | ≤90% | |
altitude | ≤1000m | |
Size | 410mm × 260mm × 340mm | |
Weight | ≤22kg |
Suppliers with verified business licenses