| After-sales Service: | 1 Year |
|---|---|
| Warranty: | 1 Year |
| Test Current Range: | 10μa-1A |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Accuracy | Cx | ±(reading×1%+1pF) |
| tgδ | ±(reading×1%+0.00040) | |
| Anti-interference index | variable-frequency anti-interference, under 200% interference can still achieve the above accuracy | |
| Capacitance Range | internal HV | 3pF~60000pF/10kV 60pF~1μF/0.5kV |
| external HV | 3pF~1.5μF/10kV 60pF~30μF/0.5kV | |
| resolution | Max: 0.001pF,4 digits | |
| tgδrange | Unlimited, resolution of 0.001%, automatically identify the tested samples of capacitance, inductance and resistance. | |
| Test Current Range | 10μA~1A | |
| Power | 2kVA | |
| Internal HV | voltage range | 0.5~10kV |
| Max output current | 200mA | |
| step-up and step-down voltage mode | Continuous smooth adjustment | |
| Test Frequency | 45,50,55,60,65Hzsingle-frequency 45/55Hz,55/65Hz,47.5/52.5Hz automatic dual variable-frequency |
|
| Frequency Accuracy | ±0.01Hz | |
| External HV | When forward wiring the max test current is 1A, power frequency or variable frequency is 40-70Hz | |
| When reverse wiring the max test current is 10kV/1A, power frequency or variable frequency is 40-70Hz | ||
| CVT self-excited method low voltage output | Output voltage 3 ~ 50V, output current 3 ~ 30A | |
| Measuring time | About 40 s, correlate with the measurement mode | |
| Input Power | 180V~270VAC,50Hz±1% | |
| Computer Interface | Standard RS232 interface | |
| Printer | A7 thermal mini printer | |
| Temperature | -10ºC~50ºC | |
| Relative Humidity | <90% | |
| Dimension | 460×360×350mm3 | |
| Weight | 28kg | |